The BDFB with the digital metering panel (P/N 008-00001-2602) ships from Telect with the shunt jumpers for reading the panels current set for an 800A shunt. Please following the installation instructions for configuring the jumpers to support your installed shunt size. If the jumpers are not properly set, you will receive incorrect current readings.