Why does my AC unit on my Telect IOE enclosure not come on?

« Go Back

Information

 
Answer
If the AC unit for your Telect Power System Enclosure (IOE-xx-xxxx) is not turning on when the temperature increases above the temperature threshold set in the controller, it could be because the output control is disabled.  The AC unit is turned on and off from the IOE controller using a digital output, which can be manually disabled.  In order to verify if this is the case, you should check that the AC unit digital output is set to "Automatic" under the Digital Output section of DC Tools or on the Controller's front panel.

If the AC unit digital output is set to "Inactive" the unit will not turn on.